12.3. Input/output functions
Inputs:
Input type Description
NONE Input is not configured to any function.
NOT IN AUTO When this input is active the controller automatism will be inhibited, fault LED will blink and screen will show
“NOT IN AUTO” to return to automatic, clear the input and press the AUTO/MAN button.
FLT-1 When this input is active controller will send and order to go and stay on position 0, during this time the alarm
led will blink as well as auto/manu led and the buzzer will sound. To clear deactivate the input and press the
Auto/manu button.
FLT-2 When this input is active controller will send and order to go and stay on position 0, during this time the alarm
led will blink as well as auto/manu led and the buzzer will sound. To clear deactivate the input and press the
Auto/manu button.
RMT POS I Order to switch to position I, will take priority over automatic mode when active. When input is deactivated, it
will return to the last working mode.
RMT POS II Order to switch to position I, will take priority over automatic mode when active. When input is deactivated, it
will return to the last working mode.
RMT POS O Order to switch to position I, will take priority over automatic mode when active. When input is deactivated, it
will return to the last working mode.
FAULT RESET
(or FLT-RESET)
Clears the ongoing fault status.
Outputs:
Output can only be congured in Main-Main application, in all other cases the output will be used for genset start (GENSET).
Output type Description
GENSET Ouput is programmed to send the Genset start signal.
NONE Output is not configured to any function.
S1 AVAIL The output signal is activated when source 1 is available.
S2 AVAIL The output signal is activated when source 2 is available.
Alarm The output is activated when the alarm LED of the controller is activated.
Pos I The output is activated whenever the ATS is in positon I.
Pos II The output is activated whenever the ATS is in positon II.
Pos 0 The output is activated whenever the ATS is in positon 0.
FireAlarm The output is activated whenever fire alarm input is activated.
12.4. Communication parameters
To access the communication parameters go to “SYSTEM” “COM”, settings are as follow:
Settings Adjustment range Default value Description
Node address 1-127 3 Product serial address
BaudRate 9600/38400/57600/115200 38400 Baud rate
Data format 8N/8O/8E/7O/7E
(1)
8N Format for serial communication
Stop Bit 1, 2 1 Stop bit for data
(1) N for no parity, O for Odd parity and E for even parity.