EN
ATySController C35 - 549781A - SOCOMEC
Manual mode
In this mode the manual orders buttons
, , enable manual orders to switch respectively to position I , 0 or II.
This mode is activated when the AUTO LED (1) is OFF, the Fault LED (12) is OFF and the screen does not indicate “NOT IN
AUTO” or “Inhibit” or the TEST LED (8) are not activated. To switch from AUTO mode to manual mode, press the
button the
screen will then prompt users to enter the password (congurable default is 1000).
After the correct password has been entered, the AUTO LED (1) should then turn ON.
Inhibit mode
In this mode both the Automatic transfer and manual orders will be blocked. This mode is activated when the programmable
inputs are programmed to “NOT IN AUTO” or “INHIBIT”.
In this mode the fault LED (12) will be blinking, and AUTO LED will be OFF and the screen will show “NOT IN AUTO” or
“INHIBIT”. To leave the inhibit mode close the input, the controller will return to previous working mode. Message on the screen
should clear automatically after input has been deactivated.
Programming mode
This mode allows product parameter conguration.
To access this mode , long press (>3s) on the
button, the screen will prompt to enter the password (Congurable, default
1000), while in the programming mode the LED 8 will be ON. To exit this mode press the (return button) until the LED 8 is OFF,
the controller will then return to the previous working mode (Auto or Manual).
10.2. Visualisation screens
The C35 has 7 visualisation screens accessible with the (navigation button short press <3s) in automatic or manual mode which
will allow users to cycle through each screen, the screen will return to screen 1 after a 30s delay.
These 7 screens give user a clear view of the installation state and parameters of the installation, do not require a password and
do not have any impact on the product’s behaviour.
Screen 1: voltage frequency and source availability:
Main screen this screen allows users to view source 1 and 2 status (lled rectangle for source available, empty for unavailable)
voltage values as well as frequency on both sources.
S1 50.1Hz
U1n=232V
S2 50.2Hz
U1n=234V
Sceen 2: voltage threshold and hysteresis settings. A global view of all the hysteresis and thresholds set on the product:
S1=OVth=116%
S1=OVhy=110%
S1=UVth=85%
S1=UVhy=95%
S2=OVth=112%
S2=OVhy=110%
S2=UVth=85%
S2=UVhy=95%