25
EN
ATySController C35 - 549781A - SOCOMEC
11.3. Outputs
11.3.1. Control signal outputs
Control signal outputs are the output orders (dry contact) to the RTSE, these outputs are rated for 250 V.a.c 50/60 Hz 5A
general use and 30 V.a.c 5A general use.
The control signal outputs logic will vary depending on the technology set in the menu “System” “TECHNO TYPE”
Techno type Order
(1)
Contact 17-16 Contact 17-15 Contact 17-14 Contact 17-13
PC / CC
Position 0 Closed Open Open NC
Position I Open Closed Open NC
Position II Open Open Closed NC
CB
Position 0 Open Closed Open Closed
Position I Closed Open Open Closed
Position II Open Closed Closed Open
(1) Orders can be given through the automatic logic of the controller in automatic mode or using the pushbuttons in manual mode
The duration of the order can be changed in the programming mode in “System” “SIGNALTIME”, the duration can be
changed from 0.1s up to 20s or changed to be maintained by going above the 20s value (default value is 5s).
From 0.1s-20s, orders are sent for duration set in "SIGNALTIME". If the RTSE does not reach the requested position in the set
time a FAULT for the corresponding position.
In CC Type technology when an order is sent it will be maintained until a different order is sent.
11.3.2. Genset start output
Genset start outputs are the output orders (dry contact), the contact between 51 and 54 will open & the
contact between 51 and 52 will close when the signal to start the genset should be sent (during a test on load
or when source 1 is lost). These outputs are rated for 250 V.a.c , 50/60 Hz 5A general use for NO contact and
3A general use for NC contact, and 30 V.d.c 5A general use for the contact between 51-54 and 3A general
use for the contact 51-52.
Control 51/54 51/52
Generator Start Contact open Contact closed
Generator Stop Contact closed Contact open
When the switch returns in position I the Cooldown timer will start counting (Default value 180s) during the cooldown timer, the
contacts will maintain the generator start signals.
CAUTION ! If the 24 V.d.c auxiliary power supply is not used the timer 1FT will not count and the order to start
the generator will be sent immediately when source 1 is completely lost.
In Main-Main mode: if “S1-Mains S2-Mains” is selected in “System” “APP” the start-gen output can be congured for other
functions in the menu I/O. see chapter "12. Programming", page 27 for possible output functions.