Annex I - 7. Priority settings & Retransfer
Priority settings to S1 or S1 can be congured in the programming mode in “System””PRIO NET” depending on the setting in
“System””RETURNS” the controller will transfer back to the priority source.
If “AUTO RETRANS” is selected the controller will automatically retransfer to the priority source once it becomes available (Return
time for this source completed).
If “MANUAL RETRANS” is selected the controller will wait for validation on the HMI before retransferring to the main source, the
screen will show the following message when waiting for user validation:
To validate press the
button.
Annex I - 8. Tests
The C35 allows for two conguration on the test button, “TEST ON LOAD” or “TEST OFF LOAD”, to change the conguration go
in programming mode “Test” “BUTTON TEST”.
To start a test do a long press (>3s) on the
button test when in manual or automatic mode the controller will request the
user password before starting the test, once the test starts the test LED will turn on. The test will stop when the user presses the
test button again for at least 3 seconds, the controller will return to the last working mode.
In Main-Main mode the genset start output will not be activated.
Sequence for TEST ON LOAD:
Allows user to test the full genset + ATS function