EasyManuals Logo

socomec ATyS r User Manual

socomec ATyS r
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
44
EN
ATYSp - 542001E - SOCOMEC
Denomination Terminal Description Characteristics Recommended
Cable Section
ATSVoltage
SensingInput*
Switch II
203 - 1/2 Phase or neutral connected on power contact 1 or 2
of Switch II
575 Vac
(ph-ph) max
332Vac
(ph-n) max
1.5 – 2.5mm
2
204 - 3/4
Phase connected on power contact 3 or 4 of Switch II
205 - 5/6
Phase connected on power contact 5 or 6 of Switch II
206 - 7/8 Phase or neutral connected on power contact 7 or 8
of Switch II
ATS Module
Programmable
Inputs
207 - Common control terminal for inputs 5 & 6,
208 – 209 and negative for optional module
extension I/O supply
Attn:
To be used with
dry contacts fed
from 207 ONLY.
1.5 – 2.5mm
2
208 Programmable Input number 5
209 Programmable Input number 6
210 + + dc Power supply for optional module
extension I/O supply
To Ext I/O Only
Motorisation
Module
Control Inputs
312 Remote Control Mode Enable when closed with 317
Attn:
Do not connect to
any Power supply
Max cable
length 100m
1.5 – 2.5mm
2
313
Position 0 order if closed with 317. (Priority order input
forcing the product to remote control mode and 0 position)
314 Position II order if closed with 317
315 Position I order if closed with 317
316 Position 0 order if closed with 317
317 Common control terminal for 312 - 316 ATyS
(Specic Voltage Supply)
ATS Module
Programmable
Inputs
413 Programmable Input number 1
Do not connect to
any power supply.
Attn:
To be used with
dry contacts fed
from 417 ONLY.
1.5 – 2.5mm
2
414 Programmable Input number 2
415 Programmable Input number 3
416 Programmable Input number 4
417
Common supply for programmable inputs 1 to 4 (413 - 416)
RemoteInterface
RJ Output to D20 remote control & display module
Up to 3m RJ 45
I/OExtension
Modules
2xInput
2xOutput
(Optional)
I 13+ Programmable Input
To be powered
from terminals
207 – 210
10 – 30VDC
1.5 – 2.5mm
2
I 14 -
I 23 + Programmable Input
I 24 -
O 13 Programmable Output
Dry Contacts 2A
AC1 / 250V
1.5 – 2.5mm
2
O 14
O 23 Programmable Output
O 24
MODBUS
Module
(Optional)
0 RS 485 MODBUS Communication module terminals
-
+
Current
transformers*
R1
Current Transformer:- I1
CT Input
2A or 1A
1.5mm²
R2
S1
Current Transformer:- I2
S2
T1
Current Transformer:- I3
T2
*For metering and sensing details, please refer to page 40.
CAUTION
Do not connect terminals 312 to 317, 413 to 417 or 207 to 209 to any power
supply. These order inputs are powered through terminal 207


Table of Contents

Other manuals for socomec ATyS r

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec ATyS r and is the answer not in the manual?

socomec ATyS r Specifications

General IconGeneral
Brandsocomec
ModelATyS r
CategorySwitch
LanguageEnglish

Related product manuals