ATYSp - 542001E - SOCOMEC
AnnexeI-11.4.Operationofloadsheddingbeforetransfer
If output LSC is selected, (load shedding before transfer request), the associated time delay LST (maximum duration
of the load shedding) must be programmed in the Timers Menu.
Scenario1withLSIactive
Source 1 Source 1
Source 2
1FT
2AT
1RT
2CT
Source 1 Source 1
Source 2
1FT
2AT
1RT
Valid from the leading edge
0DT
I
Sources
I II
ODT
Gen set start delay
Shedding
Load shed
Scenario2:LSIInputnotactivated
Source 1 Source 1
Source 2
1FT
2AT
1RT
Source 1 Source 1
Source 2
1FT
2AT
1RT
2CT
Valid from the leading edge
(Bypass Tempo LST)
0DT
Sources
ODT
II
II
Gen set start delay
Load shed
Shedding
AnnexeI-12.Communicationmenu–keypadnavigation
7
COMM
Definition AdjustmentRange
DHCP NO
Dynamic Host Conguration Protocol YES / NO
IP 1-2 192.168.
IP Address Line 1 -
IP 3-4 .002.001
IP Address Line 2 -
GAT1-2 000.000.
Gate Line 1 -
GAT3-4 .000.000
Gate Line 2 -
MSK1-2 255.255.
Mask Line 1 -
MSK3-4 .255.000
Mask Line 2 -
ADDRESS 005
ATySp Device network address: 1 to 255
BDRATE 9600
Baud rate: 9600, 19200
38400
STOP BIT 1
Stop Bit Setting 1, 2