ATYSp - 542001E - SOCOMEC
OutputCodeDefinition AdjustmentRange M-G M-M
PTS PowerThresholdExceeded(LoadShedding2):
This output signal is linked to the kva ratings as congured in the
Power Level settings menu. When the power drawn by the load
exceeds the threshold levels set output PTS will be activated so as to
load shed selected loads.
NO / NC
EES BatteryChargeOutputsignal:
This output will be activated when the maximum reset timer EET
elapses. This output may be used with a battery charger that will be
switched on depending on the Genset idle time. Output EES will be
deactivated when the battery charge run timer (EDT) elapses.
NO / NC
COP ControllerAvailable
This output is activated when the ATS controller of the ATyS p is
considered to be operational and ready to switch positions.
NO / NC
MAN Product in Manual Mode
This output is activated when the product is in Manual Mode (Selector
in MAN position).
NO / NC
Note:
The Engine Exerciser settings are only accessible through Webserver and through Easy Cong programming software.
Refer to the Easy Cong section for details.

Table of Contents

Other manuals for socomec ATyS r

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec ATyS r and is the answer not in the manual?

socomec ATyS r Specifications

General IconGeneral
Brandsocomec
ModelATyS r
CategorySwitch
LanguageEnglish

Related product manuals