97
EN
ATYSp - 542001E - SOCOMEC
EON takes priority over E2T if E2T is set as UNL (Unlimited)
EON input
Operation request
“Starting order”
contact
Pos II
Pos I
Starting time
E1T E3T
2CT
?
2AT
AnnexeI-11.3.Programmableoutputs
OutputCodeDefinition AdjustmentRange M-G M-M
S1A Source1availableoutput:
This output is activated when source 1 is available.
NO / NC • •
S2A Source2availableoutput:
This output is activated when source 2 is available.
NO / NC • •
SCA Source1orSource2availableoutput:
This output is activated when at least one source (S1 or S2) is available.
NO / NC • •
AC1 SwitchPositionIauxiliarycontact:
This output is activated when the switch is in position I.
NO / NC • •
AC2 SwitchPositionIIauxiliarycontact:
This output is activated when the switch is in position II.
NO / NC • •
AC0 SwitchPosition0auxiliarycontact:
This output is activated when the switch is in position 0.
NO / NC • •
LO1 Loadbeingsuppliedbysource1:
Indicates which source is supplying the load. This output is activated
when the switch is in Position I and Source 1 is available.
(LO1 activated = AC1 and S1A activated).
NO / NC • •
LO2 Loadbeingsuppliedbysource2:
Indicates which source is supplying the load. This output is activated
when the switch is in Position II and Source 2 is available.
(LO2 activated = AC2 and S2A activated).
NO / NC • •
LSC Loadsheddingbeforetransferoutputcommand:
This output will initiate load shedding prior to the transfer from source 1
to a backup (usually smaller) power source. After restoration this output
may also be used to signal reloading.
For further details refer to the diagrams below.
NO / NC • •
FLT Faultconditionoutput:
This output is activated when at least one type of fault (internal or
external) is activated.
NO / NC • •
POP ProductAvailable(NoFault):
This output is activated when the ATySp (ATS Controller) is considered
to be operational and ready to switch positions.
NO / NC • •
CO1
to
CO14
CopyInputtothecorrespondingOutput:
The output adopts the same state as the corresponding input.
This is the same function as relaying.
NO / NC • •
LCK ProductLockedoutput:
Output linked to the padlocked state of the ATySp. (Product in manual
mode with the padlocking mechanism pulled out.
NO / NC • •