- 29
Data Format : Float
40015 8 Password Lock 00 OE
Write any value to password lock
protected registers.
Read password lock status:
0 = locked. 1 = unlocked.
Reading will also reset the
Pass word timeout back to one
minute.
Length : 4 byte
Data Format : Float
r
40019 10
Network Parity
Stop
00 12
Write the network port parity/stop
bits for MODBUS Protocol, where:
0 = One stop bit and no parity,
default.
1 = One stop bit and even parity.
2 = One stop bit and odd parity.
3 = Two stop bits and no parity.
Requires a restart to become
effective.
Length : 4 byte
Data Format : Float
r/w
40021 11 Network Node 00 14
Write the network port node
Address: 1 to 247 for MODBUS
Protocol, default 1. Requires a restart
to become effective.
Length : 4 byte
Data Format : Float
r/w
40023 12 Pulse1 Divisor1 00 16
Write pulse divisor index: n= 0 to 5
0--0.0025 kWh(kVArh)/imp
r/w