40029
15
Baud Rate
00
1C
Write the baud rate for MODBUS Protocol,
where:
0 = 2400 baud. 1 = 4800 baud.
2 = 9600 baud, default.
3 = 19200 baud. 4 = 38400 baud.
Length : 4 byte
Data Format : Float
r/w
40063
32
CT ratio
00
3E
CT Ratio range:1~2000
CT Ratio= primary current /secondary current
Length : 4 byte
Data Format : Float
Requires password, see parameter 13
(Non MID)
r/w
40065
33
PT ratio
00
40
PT Ratio range:1~2000
PT ratio= primary voltage /secondary voltage
Length : 4 byte
Data Format : Float
Requires password, see parameter 13
(Non MID)
r/w
40087
44
Pulse 1
Energy Type
00
56
Write MODBUS Protocol
input parameter for pulse
out 1: 37 = total kwh or 39 = total kVarh,
default 39.
r/w