EasyManua.ls Logo

socomec DELPHYS MP - Structure of the Menus on the Central Bypass Cabinet

socomec DELPHYS MP
49 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS/NTA GB/DELMP_EXPC1C3C6_B 32
4.4.3 Structure of the menus on the central bypass cabinet
Load protected by inverter
1 2 3 4 5 6
Load rate:
0
50 100
120
Press "ENTER" to reach the various menus,
Select the menu with the UP
or DOWN key,
Press "ENTER" to reach the various sub-menus,
Select the sub-menu with the UP
or DOWN key,
Validate with the "ENTER" key.
LIST OF MENUS LIST OF SUB-MENUS
t
UPS SYSTEM GENERAL OUTPUT
UPS SYSTEM OUTPUT POWER
MEASUREMENTS "ENTER"4
INVERTER / BYPASS MAINS
UPS AUTOMATIC START UP
LOAD TO MAINS / LOAD TO INVERTER
TRANSFER TO MAINTENANCE BYPASS
UPS COMMANDS "ENTER"4
UPS
UNIT
EVENT LOG "ENTER"4
DIAGNOSTIC CODES
REFERENCES
BYPASS DATA "ENTER"4
UPS SYSTEM STATUS
STATUS "ENTER"4
LOAD TO MAINS / LOAD TO INVERTER
SHUTDOWN UPS OUTPUT
SUBSET COMMAND
"ENTER"4
PROGRAMMING
CLOCK "ENTER"4
LANGUAGE
BUZZER
ACCESS CODE
CONFIGURATION "ENTER"4
LOCAL / REMOTE
PROGRAMMING
u
JBUS LINK "ENTER"4
Note Controls are only displayed when available.

Table of Contents

Related product manuals