EasyManua.ls Logo

socomec ENT-RK10 - 7 Technical Data

socomec ENT-RK10
21 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TECHNICAL DATA
Q SECTION 1
16
7 TECHNICAL DATA
Technical data ENT-TW08
ENT-TW10
ENT-RK10
ENT-TW15
ENT-RK15
ENT-TW20
ENT-RK20
Power 800VA / 560W 1000VA / 700W 1500VA /1050W 2000VA /1400W
Technology VFI (Voltage and Frequency Independent) On line double conversion
Input
Input voltage 160 ÷ 276Vac (1ph)
Frequency 50/60Hz (automatic selection)
Power factor >0.97
Input current Sinusoidal absorption
Output
Output voltage (Vout)
230V (1ph) ± 3% (selectable* 220/240V)
Voltage distortion <4% on a linear load
Output frequency stability
50Hz or 60Hz (± 0.5% in battery mode)
Automatic by-pass
Voltage selected ± 15%
Overload (with mains
present)
130% for 10 seconds
AC/AC efficiency 88%
Crest factor 3:1
Reference normatives
Standard European UPS standard EN50091 and CE marking
Safety / EMC standards EN50091-1-1 / EN50091-2
Environmental data
Operating temperature 0 +40°C (32-104°F)
for longer life battery from 15°C to 25°C (59°F - 77°F )
Storage temperature (MAX) -5 +50°C (23-122°F)
Relative humidity HR 0 ÷ 90% non-condensing
Maximum altitude (above
sea level)
1,000mt (3,300ft) with no derating; maximum 3,000mt (10,000ft)
Acoustic noise (ISO 3746) < 45dB @ 1mt
Physical data (weight including batteries)
Dimensions (WxDxH) TW 145x405x225 mm 87x495x435
TW weight 14 kg 15 kg 22 kg 23kg
Dimensions (WxDxH) RK
/
483x460x87 mm 483x495x87 mm
RK weight / 16 kg 22 kg 23kg