7.5. External Battery Pack Connection
To increase the battery back-up time, you can connect several external battery
packs to the UPS. Please follow the steps below (Figure 7-5 & Figure 7-6) and
information in §5.8 External Battery Connector to complete the connection.
When connecting the external battery pack to the UPS, you must install an
appropriate non-fuse DC breaker or a fast-acting fuse that meets the safety
certication. Do not use an AC breaker.
The breaker must be a 2-pole non-fuse DC breaker with characteristics of
1-pole 250Vdc, 2-pole 500Vdc and 35kA (or above) DC breaking capacity.