SOFAR 15~24KTLX-G3 User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 50 -
ID05
GFCIFault
GFCI Fault
If the fault occurs occasionally, the possible
cause is that the external circuits are
abnormal occasionally. inverter
automatically returns to normal operating
status after the fault is rectified. If the fault
occurs frequently and lasts a long time,
check whether the insulation resistance
between the PV array and earth(ground) is
too low, then check the insulation
conditions of PV cable.
ID06
OVRT
OVRT faulty
There are internal faults of inverter, turn
OFF the DC switch, wait for 5 minutes,
then turn ON the DC switch. Check
whether the fault is rectified. If no, please
contact technical support.
ID07
LVRT
LVRT faulty
ID08
IslandFault
Islanding
faulty
ID09
GridOVPInst
ant1
Grid
instantaneous
voltage too
high 1
ID10
GridOVPInst
ant2
Grid
instantaneous
voltage too
high 2
ID11
VGridLineFa
ult
Grid Line
voltage Faulty
ID12
InvOVP
Inverter
overvolatge
ID17
HwADFaultI
Grid
The grid
current
sampling error