SOFAR 7K~10.5KTLM-G3 User manual
Copyright © Shenzhen SOFAR SOLAR Co., Ltd
27.S1 threshold 195.5V
1500ms
27.S2 threshold 34.5V 200ms
81>.S1 threshold 50.5Hz
100ms
81>.S2 threshold 51.5Hz
100ms
81<.S1 threshold 49.5Hz
100ms
81<.S2 threshold 47.5Hz
100ms
15. Autotest STD
The test procedure is same as Autotest Fast, but it’s much more time consuming.
(B) “Event List” Interface as below:
Event List is used to display the real-time event records, including the total
number of events and each specific ID No. and happening time. User can enter
Event List interface through main interface to check details of real-time event
records, Event will be listed by the happening time, and recent events will be
listed in the front. Please refer to below picture. Long press the “∨” enter into
main menu interface, and short press the “∨” to turn the page in standard
interface, then enter into “2.Event List” interface.