EasyManua.ls Logo

sol-ark 8K - Component Distance Guide; Decide Critical Backup Circuits

sol-ark 8K
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
August 3, 2019 4
3. Component Distance Guide
WIRE RUN LENGTH: SEE DIAGRAM FOR WIRE GAUGE (AWG) RECOMMENDATIONS, PAGE 11 FOR COMPLETE DETAIL
4. Decide Critical Backup Circuits
a. Decide which 10 circuits will be on backup power continuously. These circuits must use non-
GFI breakers to work with the transfer switch. You can replace a GFI breaker with a normal
breaker, installing GFI outlets instead (or you can move GFI breaker into 10-circuit SW). If
applicable, low load circuits can be combined.
b. Important: Make sure to keep within inverter amperage limits:
On Grid = 50A continuous
Off Grid = 33A continuous/83A peak
c. Verify each load circuit by measuring typical and max Amps with a clip-on Amp meter. Amps x
120V = Watts
IF PROGRAMMED TO SMART LOAD
DO NOT CONNECT GENERATOR TO GEN PORT

Other manuals for sol-ark 8K

Related product manuals