August 3, 2019 40
10. Turn on PV input and AC Grid inputs.
11. Did you setup Wi-Fi plug to the customer’s internet? Y/N
12. Absolutely important for software updates. Did you help customer register system on Monitoring App? Y/N
13. Does customer have a standby generator or small portable generator? Y/N
a. Did you turn off UL1741/IEEE1547 (use General Standard) and reprogram grid freq range to 53-65Hz? Y/N
b. If standby generator, are the current limit sensors on the Grid side of the generator transfer switch? Y/N
c. If small gas generator using Gen inputs, did you enable Gen charging and properly set charge current? Y/N
14. If EMP protected, did you install EMP Suppressors on critical appliance cords? Y/N
_______________________ _______________________ ____________________
Installer Name Installer Signature Date
_______________________ _______________________ ____________________
Customer Name Customer Signature Date
In Limited To Home Mode
HM values will be close to
zero. HM values should
never be negative. If
negative, the Limiter
Sensors are not installed
properly.