66
L20, L30
Model
L20
L30
Battery test
Manual and automatic programmable by time or voltage
Decentralized battery in
parallel mode
Support
Output
Overload
Online mode
110% 60mins, 125% 10mins, 150% 1mins
Battery
mode
110% 60mins, 125% 10mins, 150% 1mins
THDU
Linear load
2%
Non-linear
load
4%
Output PF
1
Output voltage
380/400/415Vac (3Ph+N+PE)
Static regulation of output
±1%
Slew rate -Maximum
frequency variation
0.5~2Hz/s
Bypass source voltage
windows setup and Frequency
windows setup
Frequency±10%±5%, ±4%, ±2%, ±1%
220Vac Max.voltage: +25%(optional +10%,+15%,+20% )
230Vac Max.voltage: +20%(optional +10%,+15% )
240Vac Max.voltage: +15%(optional +10% )
Min. voltage: -45% (optional -10%, -15%, -20%, -30%)
Output voltage compensation
(support downstream
transformer)
-5%~+5%
Output rate current
30/29/28A
46/44/42A