41
L30US-IB80, L30US-IB00, L40US UPS
Power Supply Upon BYP SCR Overtemp: Specifies whether to start Bypass mode in case of
overheating. The default value is Enable.
Bypass Switches Limit: Cross currents occur during the transfer between Bypass mode and
Normal mode, which impacts the system. This parameter specifies the number of transfers
between Bypass mode and Normal mode within 1 hour, which ensures system security. The
value range is 3 to 10, default is 10.
EPO Transfers To BYP: Specifies whether to transfer to Bypass mode when the EPO button
is pressed. The default value is Disable.