55
L30US-IB80, L30US-IB00, L40US UPS
4.4. Display messages and troubleshooting
This section lists the event and alarm messages of the UPS. The messages are listed in
alphabetical order.
4.4.1. Operational status and mode(s)
Table 6 Operational status and mode(s)
AUDIBLE ALARMS DISPLAY LEDS
UPS Modes
Alarm
Status
Mutable
On/Off
Online
Alarm
Bypass
Battery
Inverter
UPS Initialization
Beeps, Only
ring once
No Blink/0.5s Blink/0.5s Blink/0.5s Blink/0.5s
UPS Online Mode
(Normal)
NO Beeps
NO
Beeps
Off Off Off On
UPS Battery Mode Beeps/2s Yes Off Off On Off
UPS Battery test Mode NO Beeps
NO
Beeps
Off Off On Off
UPS ECO Mode NO Beeps
NO
Beeps
Off On Off Off
UPS Standby Mode NO Beeps
NO
Beeps
Off Off Off Off
UPS Static Bypass
Mode
NO Beeps
NO
Beeps
Off On Off Off
UPS Maintenance
Bypass Mode
NO Beeps
NO
Beeps
Off On Off Off
UPS Frequency
Converter Mode
NO Beeps
NO
Beeps
Off Off Off On
UPS Load Overload Beeps/1s Yes Off Off Off Blink/2s
UPS Warnings
Beeps/2s or
Beeps/1s
Yes Blink/2s Blink/2s Off On