Technical Specifications - Three Phase Inverters
(Europe &APAC)
SE4K - SE12.5K
SE3K SE4K SE5K SE6K SE7K SE8K SE9K SE10K SE12.5K Unit
Output
Rated AC power
output
3000
(1)
4000
(1)
5000
6000
(1)
7000 8000 9000 10000 12500 VA
Maximum AC
power output
3000 4000 5000 6000 7000 8000 9000 10000 12500 VA
AC output voltage
– line to line / line
to neutral
(nominal)
380/ 220; 400/ 230 Vac
AC output voltage
range
184 – 264.5 Vac
AC frequency 50/60 ± 5 Hz
Maximum
continuous
output current
(per phase)
5 6.5 8 10 11.5 13 14.5 16 20 A
Maximum
continuous
overcurrent
protection
5 6.5 8 10 11.5 13 14.5 16 20 A
Residual current
detector /
Residual Current
step detector
300 / 30 mA
Grid supported –
three phase
3 / N / PE (WYE with Neutral)
Inrush current AC
(Peak/Duration)
3/ 20
Aac
(rms)
/ ms
Maximum output
fault current
26 26 51 51 51 51 61 A
(1)
Available in some countries; refer to the Certifications category in
http://www.solaredge.com/groups/support/downloads
Technical Specifications - Three Phase Inverters (Europe &APAC) 101