SE3K SE4K SE5K SE6K SE7K SE8K SE9K SE10K SE12.5K Unit
Power factor
range
1 (adjustable from -0.9 to +0.9)
Total harmonic
distortion
< 3%
Protective class Class I
Utility monitoring,
islanding
protection,
configurable
Power Factor,
country
configurable
thresholds
Yes
Overvoltage
category
III
Input
Maximum DC
power (Module
STC)
4050 5400 6750 8100 9450 10800 12150 13500 16850 W
Transformer-less,
ungrounded
Yes
Maximum input
voltage
900 Vdc
Nominal DC input
voltage
750 Vdc
Maximum input
current
5 7 8.5 10 12 13.5 15 16.5 21 Adc
Maximum back-
feed current
0 Adc
Reverse-polarity
protection
Yes
Ground-fault
isolation detection
700kΩ Sensitivity
Overvoltage
category
II
Maximum inverter
efficiency
98 %
European
weighted
efficiency
96.7 97.3 97.3 97.3 97.4 97.6 97.5 97.6 97.7 %
Night-time power
consumption
< 2.5 W
Three Phase System MAN-01-00507-4.2
102Technical Specifications - Three Phase Inverters (Europe &APAC)

Table of Contents