115
Parameter Unit Rest of the world
t f max 1 ms 500
f min 2 Hz 0
t f min 2 ms 0
f max 2 Hz 0
t f max 2 ms 0
df/dt max Hz/s 0
Ierr max mA 300
Iac mean max mA 1000
Restart delay s 0
Mains check On/Off On
- Vac MC max V 264
- Vac MC min V 196
- f MC max Hz 51
- f MC min Hz 47
- t MC monitoring s 30
Island Detection On/Off On
Soft Start W/s 0
Pac progression %/min 0
P(f)-Mode On/Off -
- f start Hz -
- f stop Hz -
- Reduction %/Hz -
- Re-increase %/min -
Q-Mode Off
- Vac Lock On/Off -
- Vac Lock-In V -
- Vac Lock-Out V -
FRT On/Off -
- K factor -
S max SM8MT2 VA 8000
S max SM10MT2 VA 10000
S max SM13MT2/3 VA 13000
S max SM15MT2/3 VA 15000
Pac max SM10MT2 W 8000
Pac max SM8MT2 W 10000
Pac max SM13MT2/3 W 13000
Pac max SM15MT2/3 W 15000
Iac max SM8MT2 A 12
Iac max SM10MT2 A 16
Iac max SM13MT2/3 A 20
Iac max SM15MT2/3 A 22