6 Wiring
6 Wiring
Current terminal connection and communication cable, connecting BMS and
inverter, shall be made before conducting wiring.
6.1 Current Terminal Connection
The steps for making current terminal connection are shown as follows:
Step 1: Strip the cable jacket about 8 to 10 mm from the end;
Step 2: Cut the heat-shrink tubing to about 28 to 30 mm long, carefully slide it
onto the end of the cable, and then carefully slip the wires all the way into the
current terminal;
Step 3: Crimp the terminal, and heat the heat-shrink tubing after it wraps the end
of terminal;
Step 4: Connect the assembled grounding cable to BMS, and then tighten the
screw.
1
6.4 mm
Length=8-10 mm
4-6 mm²
2
Length=28-30 mm
Heat-shrink tubing
43
4.5-5 N·m
*Note: The grounding cable should be prepared by the users themselves.