Technical DataTechnical Data
4.2 AC Output
Max. AC output apparent power [VA]
Nominal AC voltage [V]
Nominal grid frequency [Hz]
Nominal AC output current [A]
Max. AC output current [A]
Inrush current [A]
THDi, rated power [%]
Displacement power factor
Feed-in phase
5000
5500
13.2
14.5
6000
6600
15.8
17.4
Model
27
<3%
0.8 leading ~ 0.8 lagging
Three-phase
8000
8800
21
23.1
3~/N/PE, 220/380, 230/400
X3-MIC-6K-G2-LV X3-MIC-8K-G2-LVX3-MIC-5K-G2-LV
Nominal AC output
apparent power [VA]
4.3 Efficiency, Safety and Protection
Max. AC output apparent power [VA]
Nominal AC voltage [V]
Nominal grid frequency [Hz]
Nominal AC output current [A]
Max. AC output current [A]
Inrush current [A]
THDi, rated power [%]
Displacement power factor
Feed-in phase
3000
3300
4.6/4.4
4.8
4000
4400
6.1/5.8
6.4
5000
5500
7.6/7.3
8.0
6000
6600
9.1/8.7
9.6
Model
10000
11000
15.2/14.5
16.0
27
<3%
0.8 leading ~ 0.8 lagging
Three-phase
8000
8800
12.2/11.6
12.8
3~/N/PE, 220/380, 230/400
50/60 (±5)
12000
13200
18.2/17.4
19.1
15000
15000
22.7/21.8
22.7
X3-MIC-3K-G2 X3-MIC-4K-G2
X3-MIC-6K-G2 X3-MIC-8K-G2 X3-MIC-12K-G2X3-MIC-10K-G2 X3-MIC-15K-G2X3-MIC-5K-G2
Nominal AC output
apparent power [VA]
50/60 (±5)
3~/N/PE, 127/220
MPPT efficiency
Euro efficiency
Max. eciency
Safety & Protection
Over/under voltage protection
DC isolation protection
Grid monitoring
DC injection monitoring
Back feed current monitoring
Residual current detection
Anti-islanding protection
Over heat protection
Inverter+BMU
YES
YES
YES
YES
YES
YES
YES
YES
Model
X3-MIC-6K-G2 X3-MIC-8K-G2 X3-MIC-12K-G2X3-MIC-10K-G2
X3-MIC-15K-G2
X3-MIC-5K-G2
MPPT efficiency
Euro efficiency
Max. eciency
Safety & Protection
Over/under voltage protection
DC isolation protection
Grid monitoring
DC injection monitoring
Back feed current monitoring
Residual current detection
Anti-islanding protection
Over heat protection
Inverter+BMU
99.90%
97.80%
98.30%
YES
YES
YES
YES
YES
YES
YES
YES
Model
X3-MIC-6K-G2-LV X3-MIC-8K-G2-LVX3-MIC-5K-G2-LV
X3-MIC-3K-G2 X3-MIC-4K-G2
99.90%
97.80%
98.30%
14 15
Arc-fault circuit interrupter(AFCI)
AC auxiliary power supply(APS)
Optional
Optional
SPD protection
YES
Arc-fault circuit interrupter(AFCI)
AC auxiliary power supply(APS)
Optional
Optional
SPD protection
YES