98
Operation on LCD
Region Australia A Australia B Australia C New Zealand
Standarad
Code Name
AS4777_2022
_A
AS4777_2022
_B
AS4777_2022
_C
New Zealand
Setting
Range
OV-G-F1 52 Hz 52 Hz 55 Hz 55 Hz 50-55 Hz
OVGF1-T 0.1 s 0.1 s 0.1 s 0.1 s
OV-G-F2 52HZ 52HZ 55HZ 55HZ 50-55 Hz
OVGF2-T 0.1 s 0.1 s 0.1 s 0.1 s
UN-G-F1 47 Hz 47 Hz 45 Hz 45 Hz
40-50
Hz
UNGF1-T 1.5 s 1.5 s 5 s 1.5 s
UN-G-F2 47 Hz 47 Hz 45 Hz 45 Hz
45-50
Hz
UNGF2-T 1.5 s 1.5 s 5 s 1.5 s
Startup-T 60 s 60 s 60 s 60 s
15-1000
s
Restore-T 60 s 60 s 60 s 60 s 15-600 s
Recover-
VH
253 V 253 V 253 V 253 V
Recover-VL 205 V 205 V 205 V 198 V
Recover-FH 50.15 Hz 50.15 Hz 50.15 Hz 50.15 Hz
Recover-FL 47.5 Hz 47.5 Hz 47.5 Hz 47.5 Hz
Start-VH 253 V 253 V 253 V 253 V
Start-VL 205 V 205 V 205 V 198 V
Start-FH 50.15 Hz 50.15 Hz 50.15 Hz 50.15 Hz
Start-FL 47.5 Hz 47.5 Hz 47.5 Hz 47.5 Hz
Setting Charger
The inverter is compatible with lithium-ion battery. You can set the charge & discharge
parameters of battery.
• Max Charge: Maximum charging current of battery
• Max Discharge: Maximum discharging current of battery
• Charger upper limit: Default: 60%, range: 10%-100%
»
The maximum battery SOC when charging.