4) Grid Services
Usually end user do not need to set the grid parameters. All default value
have been set before leaving factory according to safety rules.
If reset is needed, any changes should be made according to the
requirements of local grid.
>P (freq)
Soft Start
Grid Service
P(freq)
Soft Start
Soft Start_Slope
1.
3.
9%
> P(Overfreq)
P(Underfreq)
>Disable <
> Enable/Disable
If reset is needed, any changes
should be made according to the
requirements of local grid.
If reset is needed, any changes
should be made according to the
requirements of local grid.
If set as shown, 9 percent of the
rated power increase per minute.
Reactive Power
4-1.
>Off <
> Mode Select
If reset is needed, any changes
should be made according to the
requirements of local grid.
70 71
NOTE!
The terms shown in the interface depend on the local
safety regulations.