O
owensseanSep 18, 2025
What to do if SOLIS S6-EH3P5K2-H Inverter shows over DC injection error?
- KKathleen TorresSep 18, 2025
If your SOLIS Inverter is showing an over DC injection error, restart the inverter.

What to do if SOLIS S6-EH3P5K2-H Inverter shows over DC injection error?
If your SOLIS Inverter is showing an over DC injection error, restart the inverter.
What does 'OV-Vbackup' mean on my SOLIS S6-EH3P5K2-H Inverter and how to fix it?
The 'OV-Vbackup' error on your SOLIS Inverter indicates an over-voltage issue with the backup. Check whether the backup port wiring is normal. If the issue persists, restart the system.
What does 'OV-TEM (1032 DATA:0000)' mean on my SOLIS S6-EH3P5K2-H and how do I resolve it?
If your SOLIS Inverter displays 'OV-TEM (1032 DATA:0000)', it indicates a temperature issue. Check whether the surrounding environment of the inverter has poor heat dissipation and confirm whether the product installation meets the requirements.
What does LmtByEPM mean on my SOLIS Inverter?
If your SOLIS Inverter is showing 'LmtByEPM', confirm the inverter is connected to an external EPM/meter to prevent reverse current. Also, check if the inverter is controlled by an external third-party device and verify if the power setting of the inverter power control is limited. You may also need to verify settings in section 6.6.7 and check your meter readings.
What does 12Power-FAULT mean on SOLIS S6-EH3P5K2-H?
If your SOLIS Inverter displays '12Power-FAULT (1038 DATA:0000)', check for current leakage to ground, verify your grounding, and ensure all wires are in good condition and not leaking current to ground.
What does BatName-FAIL mean on SOLIS Inverter?
If your SOLIS Inverter displays 'BatName-FAIL', confirm that the battery model selection is consistent with the actual battery you are using.
What does Fan Alarm mean on SOLIS S6-EH3P5K2-H?
If your SOLIS Inverter displays 'Fan Alarm', check if the internal fan is working correctly or if it is jammed.
What to do if my SOLIS S6-EH3P5K2-H Inverter displays ARC- FAULT (1041 DATA:0000)?
If your SOLIS Inverter shows the ARC- FAULT (1041 DATA:0000) error, verify that all connections within your PV system are tight. If further adjustments are necessary, arc fault settings can be changed in the advanced settings.
What to do if SOLIS Inverter says battery not connected?
If the SOLIS Inverter displays that the battery is not connected, verify that the battery is correctly connected and that the battery contactor is not disconnected. Restart the battery after checking the connections.
What does 'BatName-FAIL' mean on my SOLIS S6-EH3P5K2-H Inverter and how to resolve it?
If your SOLIS Inverter displays 'BatName-FAIL', confirm whether the battery model selection is consistent with the actual one.
| Model | S6-EH3P5K2-H |
|---|---|
| Type | Hybrid Inverter |
| Rated Power | 5 kW |
| Max. Input Voltage | 600 V |
| Number of MPPT Trackers | 2 |
| Rated AC Output Power | 5 kW |
| Max. AC Apparent Power | 5.5 kVA |
| Rated Grid Frequency | 50/60 Hz |
| Total Harmonic Distortion (THD) | <3% |
| Power Factor | 0.8 leading to 0.8 lagging |
| DC Switch | Integrated |
| Protection Degree (IP) | IP65 |
| Operating Temperature Range | -25°C to +60°C |
| Topology | Transformerless |
| Weight | 25 kg |
| Cooling Method | Natural Convection |
| Protection Class | Class I |
| Efficiency | 98.2% |
| Max. DC Input Power | 6.5 kW |
| MPPT Voltage Range | 90-550 V |
| Rated Grid Voltage | 230 V / 400 V |
| Grid Voltage Range | 180 V - 280 V |
| Communication | RS485, WiFi |












Loading...