6. Operation6. Operation
Table 6.1 Information list
V_DC1 350.8V
I_DC1 5.1A
V_Grid 230.4V
I_Grid 8.1A
Status: Generating
Power: 1488W
Grid Frequency
F_Grid 60.06Hz
Total Energy
0258458 kwh
This Month: 0123kwh
Last Month: 0123kwh
Today: 15.1kwh
Yesterday: 13.5kwh
10 sec
10 sec
10 sec
10 sec
10 sec
10 sec
10 sec
V_DC1: Shows input 01 voltage value.
I_DC1: Shows input 01 current value.
V_Grid: Shows the grid's voltage value
I_Grid: Shows the grid's current value.
Status: Shows instant status of the Inverter.
Power: Shows instant output power value.
F_Grid: Shows the grid's frequency value.
Total generated energy value.
This Month: Total energy generated this month.
Last Month: Total energy generated last month.
Today: Total energy generated today.
Yesterday: Total energy generated yesterday.
Display
Duration
Description
Inverter SN
00000000000000
10 sec
10 sec
Display series number of the inverter.
Power of EPM.
Current of EPM.
V_D C2 350.8V
I_D C2 5.1A
10 sec
V_D C2: Shows input 02 voltage value.
I_D C2: Shows input 02 current value.
10 sec
Work Mode .: The work mode of inverter
- .DRM Number: Show the number 01 08
Work Mode: NULL
DRM Number: 08
10 sec
10 sec
Meter EnergyP: The active power.
The status is meaningful only where “G100 Issue
2 amendment 2is applicable. See 6.5.12.7.
1. Status1: G100Set On, normal operation.
2. Status2: G100Set On, actual current is larger
than the Backflow Current.
3. Status3: G100Set On, with an operation fault
defined in the G100 standard.
4. Status4: G100Set Off.
Meter EnergyP
0000000.00kWh
G100 EPM Status
Status4
Export_P: +0000W
Export_I: 00.0A
Pressing the ESC key returns to the Main Menu. Pressing the ENTER key locks
(Figure 6.2(a)) or unlocks (Figure 6.2 (b)) the screen.
6.2.1 Lock screen
5.2 Stop the Inverter
(b)(a)
Figure 6.2 Locks and Unlocks the Screen of LCD
The following submenus are displayed when the Settings menu is selected:
1. Set Time
2. Set Slave Addr
6.3 Settings
6.3.1 Set Time
This function allows time and date setting. When this function is selected, the LCD will
display a screen as shown in Figure 6.3.
NEXT=<ENT> OK=<ESC>
01-01-2020 00:00
Figure 6.3 Set Time
Press the UP/DOWN keys to set time and data. Press the ENTER key to move from one
digit to the next (from left to right). Press the ESC key to save the settings and return to
the previous menu.
6.3.2 Set Slave Addr
This function is used to set the address when muti inverters are connected to single monitor.
The address number can be assigned from “01to “99.
The default address number of Solis S6 Single Phase Inverter is “01.
YES=<ENT> NO=<ESC>
Slave Addr: 01
Figure 6.4 Set Address
Press the UP/DOWN keys to set the address. Press the ENTER key to save the settings.
Press the ESC key to cancel the change and return to the previous menu.
.29..28.