When 1 or more inverters are installed in one location, a minimum 12inchs clearance
should be kept between each inverter or other object. The bottom of the inverter should
be 20inchs clearance to the ground.
Visibility of the LED status indicator lights and the LCD located at the front panel of
the inverter should be considered.
Adequate ventilation must be provided if the inverter is to be installed in a confined space.
NOTE:
Nothing should be stored on or placed against the inverter.
300mm300mm 300mm
Figure 4.2 Inverter Mounting clearance
Install vertically with a maximum incline of +/- 5°.If the mounted inverter is tilted to an
angle greater than the maximum noted, heat dissipation can be inhibited, and may
result in less than expected output power.
4. Installation4. Installation
.10. .11.
4.2 Mounting the Inverter
Please see Figure 4.4 and Figure 4.5 for instruction on mounting the inverter.
Figure 4.3 Inverter wall mounting
The inverter shall be mounted vertically. The steps to mount the inverter are listed below:
Suitable fixing screws
Bracket
1. According to the figure 4.2, select the mounting height of the bracket and mark the
mounting holes. For brick walls, the position of the holes should be suitable for the
expansion bolts.
Dimensions of wall bracket:
500mm
500mm
300mm
300mm
Figure 4.4 Inverter wall mounting