6. Operation6. Operation
6.5.12.7 G100Set
NOTE:
The function is only used for installations where the standard ā€œG100 Issue 2
amendment 2ā€is applicable.
There are 5 settings under G100Set:
1. G100 ON/OFF
2. Backflow Current
3. Clear Fault
4. System Type
5. Advanced Reset
6.5.12.7.1 G100 ON/OFF
Select Meter or CT according to the actual installation to turn on the function, select OFF to
disable the function.
Figure 6.37 G100 ON/OFF
YES=<ENT> NO=<ESC>
CLS Ctl Set: CT
YES=<ENT> NO=<ESC>
CLS Ctl Set: Meter
YES=<ENT> NO=<ESC>
CLS Ctl Set: OFF
6.5.12.7.2 Backflow Current
Set the desired backflow current value, and the inverter will control its power to make sure the
grid backflow current less than this value.
Figure .6 38 Backflow Current
YES=<ENT> NO=<ESC>
Current: 016A
6.5.12.7.3 Clear Fault
When there is a G100 Status3 message(See 6.2), enter Clear Fault and select YES to handle
the alarm. After the operation, the inverter will restart automatically.
Figure .6 39 Clear Fault
Are you sure?
YES=<ENT> NO=<ESC>
6.5.12.7.4 System Type
The function is used to select the PV installation type, for a domestic installation, select Resi;
For others, select NonResi.
Figure 6.40 System Type
YES=<ENT> NO=<ESC>
Reset Type: Resi
YES=<ENT> NO=<ESC>
Reset Type: NonResi
6.5.12.7.5 Advanced Reset
This function is applicable by maintenance personnel only.
6.5.13 External EPM Set
Figure 6.41 External EPM Set
->5G-EPM
Others-EPM
This setting should only be turned on when Solis external EPM device is used.
Two options are available:5G-EPM and Others-EPM.
5G-EPM Failsafe Option should be turned ON when 5G series EPM device is used
Others-EPM Failsafe Option should be turned ON when 2G series EPM device is used
Only one option can be activated each time.