MPI-520 – USER MANUAL
The meter is
ready for meas-
urement.
Make measurement by pressing START
push-button
The result is displayed on the screen for 20s.
The result can be recalled by pressing ENTER push-button.
Remarks:
- The result can be stored in the memory (see point 4.1).
- When many measurements are made in short time intervals, the meter may emit a large amount of
heat. As a result of this, the housing of the device may become hot. This is a normal phenomenon and
the meter is equipped with the protection against excessive temperature. After approximately 15 con-
secutive measurements of short circuit loop, wait until the instrument cools down. This limitation results
from the high current measurement and multi-functionality of the meter.
- Minimum interval between successive measurements is 5 seconds. This minimum interval requirement
is controlled by the meter. A next measurement can be made only when READY! message appears on
the screen.