MPI-520 – USER MANUAL
Resolution
[W], [VA], [var]
Basic uncertainty (with regard to
apparent power S)
*)
Voltage range: 0…500 V
Current range: 0...400 A
Nominal network frequency f
n
: 50 Hz, 60 Hz
Number of phases of the circuit tested: 1
Range of cosφ display: 0.00..1.00 (resolution 0.01)
*) U: 50…500 V, I: 10 mA…400 A
Error of clamp must be additionally taken into account
Measurement of short circuit loop impedance Z
L-PE
, Z
L-N
, Z
L-L
Measurement of short circuit loop impedance Z
S
Test range according to IEC 61557:
Display range:
Nominal working voltage U
nL-N
/ U
nL-L
: 110/190 V, 115/200 V, 127/220 V, 220/380 V, 230/400 V,
240/415 V
Working range of voltage: 95…270 V (for Z
L-PE
and Z
L-N
) and 95…440 V (for Z
L-L
)
Nominal network frequency f
n
: 50 Hz, 60 Hz
Working range of frequency: 45…65 Hz
Maximum test current (for 415 V): 41.5 A (10 ms)
Control of correctness of PE terminal connection by means of a touch electrode
Indications of short circuit loop resistance R
S
and short circuit loop reactance X
S
(5% + 5 digits) of Z
S
value
Calculated and displayed for a value of Z
S
<20