10.7 Output technical data
Probe cleaning
Maximum voltage 32 Vdc
Drive CONSTANT (dc) or PULSED, 1 second on, 1 second off.
4-20 mA(s)
Minimum current 0 mA
Maximum current 20 mA
Open circuit voltage (maximum) 19 Vdc
Resolution 0.1% FSD
Maximum output load 500 ohm
Isolation 100 V
Output rate 10 / second
Relay(s)
Contacts 2 x single pole changeover relays (SPCO)
Voltage ratings (maximum) 250 Vac
Resistive load 3 amp @ 250 Vac
Inductive load 1 amp @ 250 Vac
ac motor load
¼ HP (2.9 amp) @ 250 Vac
1
/
10 HP (3 amp) @ 120 Vac
Pilot duty load C300 (2.5 amp) - control circuit / coils
Electrical life (operations) 3 x 10
5
or greater depending on load
Mechanical life (operations) 30 x 10
6
RS485
Physical layer RS485 4-wire full or 2-wire half duplex
Protocol Modbus RTU format
Isolation 60 Vac / dc
Receiver unit load (256 devices - maximum)
Output rate Up to 10 frames / second
Infrared
Physical layer IrDA
Baud 38400
Range 10 cm
Working angle 15°
Eye safety information
Exempt from EN 60825-12: 2007 Safety of laser
products ~ does not exceed the accessible emission
limits (AEL) of class 1