10.8 Default settings
10.8.1 MODE MENU
Allows the valve to be manually opened or closed
Ranges OPEN or CLOSE
Default CLOSE
10.8.2 DATA MENU
TEMP (temperature units)
Ranges °C or °F
Default °C
UNITS (TDS or conductivity units)
Ranges µS / cm or ppm
Default µS / cm
PH TERM
Ranges 0.50 - 1.00
Default 0.7
Resolution (steps) 0.01
Assuming µS / cm to ppm conversion = 0.7
10.8.3 INPUT MENU
T COMP (Temperature compensation)
Ranges 100 - 250 °C or 212 - 482 °F
Default 184 °C (10 bar g) or 363 °F
Resolution (steps) 1°
Units °C or °F
TDS - SENSOR (Probe selection)
Ranges CP10, CP30, CP32
Default CP10