IM-P403-89 EMM Issue 8
65
TDS - SENSOR - FLT MODE (Fault mode) Only available if CP32 is selected
Ranges OFF, ALARM, CLEAN or AL+CLEAN
Default OFF
CLEAN or AL+CLEAN is only available if a clean duration is selected
TDS - PURGE – DURATION (Purge time)
Ranges 0 - 180
Default 000
Resolution (steps) 1
Units Seconds
TDS - PURGE – INTERVAL (Time between purges)
Ranges 10 - 60
Default 30
Resolution (steps) 1
Units Minutes
TDS - PURGE – BURNER (Purge time dependant on time or burner firing time)
Only available if PURGE - DURATION is greater than 0 seconds.
Ranges Normal or Cumulative
Default Cumulative
TDS - FILTER
Only available if PURGE - DURATION is = 0 seconds
Ranges ON or OFF (TC = 64 or 8* seconds)
Default ON
*8 second filter, also includes a 5% (FSD) Jump out function for CCD systems
TDS - RANGE
Ranges 9.99, 99.9, 999, 9990
Default 9990
Units µS / cm or ppm