69
10.8.5 TIMER MENU - Bottom blowdown (BB)
DURATION (bottom blowdown valve open time)
Ranges 0 – 999
Default 0
Resolution (steps) 1
Units Seconds
INTERVAL (Time between bottom blowdown)
Only available if TIMER DURATION is greater than 0 seconds
Ranges 1 - 99
Default 12
Resolution (steps) 1
Units Hours
SWITCH (If a switch is fitted to valve, select fitted)
Only available if TIMER DURATION is greater than 0 seconds
Ranges FITTED or NONE
Default FITTED
CLOSING (Time allowed for valve to close)
Only available if TIMER DURATION is greater than 0 seconds
Ranges 1 – 10
Default 5
Resolution (steps) 1
Units Seconds
LIFT (Time allowed for valve to lift off the seat)
Only available if TIMER DURATION is greater than 0 seconds
Ranges 1 – 10
Default 5
Resolution (steps) 1
Units Seconds
MODE (Allow the valve to be manually opened, closed or automatically opened
and closed under the control of the timer)
Only available if TIMER DURATION is greater than 0 seconds
Ranges AUTO, OPEN, OFF
Default AUTO