IM-P403-89 EMM Issue 8
72
OUTPUT – VALVE (Opens or closes blowdown valve manually)
Ranges ON or OFF
Default ON
Press the
OK
button to activate relay – Automatic control of relays is selected by
selecting cancel or after 5 minutes has elapses.
OUTPUT – BB VALVE (Opens or closes bottom blowdown valve manually)
Only available if TIMER – DURATION is > 0.
Ranges ON or OFF
Default ON
Press the
OK
button to activate the relay – Automatic control of relays is selected by
selecting cancel or after 5 minutes has elapses.
OUTPUT – ALARM 1 (Energises or de-energises the alarm relay manually)
Ranges ON or OFF
Default ON
Press the
OK
button to activate the relay – Automatic control of relays is selected by
selecting cancel or after 5 minutes has elapses.
SET PASS MENU (Set pass code)
Ranges 0000 - 9999
Default See Section 2
TREND MENU (Sets time base of trend graph)
Ranges MINS, HRS, DAYS
Default MINS