IM-P337- 6 9 EMM Issue 2
45
7.4.3.1 PRES 0 CAL (ZP)
When entering the PRES SENSR menu the 0CAL menu will be displayed. Pressing the right arrow key (>)
will display the 0CAL bits values.
When the bits values for the 0 CAL have been entered press the OK button to confirm.
7.4.3.2 PRES 25 CAL (EP)

every pressure sensor kit lists the 25CAL bits values that are required to be entered into this menu.

7.4.4 tEMP SENSR
This allows the user to add an external temperature sensor, which in turn will enable two modes of
operation, steam and heat.
7.4.4.1 StEAM
When in steam mode the MVT10 will operate seamlessly between saturated and superheated steam.
7.4.4.2 HEAt
When configured in the heat mode, the MVT10 will display the net energy usage of the process. It assumes
by default that 100% of the steam is converted to condensate, but can be configured.