IM-P337- 6 9 EMM Issue 2
63
Menu Default Range, options
Basic Data
Dryness fraction 97 % Range 70 to 100 %
Units Metric Metric, imperial
tOtAL Mass Mass, ENRGy
Atmospheric pressure 1.01 bar a 0.7 - 1.10 bar a
Scale Large/small Small
Input
OUtPUtS
4-20 mA
Source FLOW FLOW, POWER
Set 4 mA 0 0 to one below max value
Set 20 mA Max
MAX - flow a @ 32 bar g (Tonne/h)
DN150: 22.38
DN200: 43.99
DN25 0: 6 0.14
DN300: 85.37
MAX - Power @ 32 bar g (MW)
DN150: 17.43
DN200: 34.26
DN250: 46.83
DN300: 66.48
Pulse yES yES, NO
Source tOtAL ToTal, ENRGy
NUM/PULSE 0.01
In (default) small units this is
1, 10, 100, 1 000, 10 000.
PULSE WidtH 0.2 Sec Range: 0.02 -0.2 Sec
COMMS
Baud 9600 baud 1 200, 9 600, 19 200
Add 001 Range: 001 to 247
Parity None None, Even, Odd
Delay 0.00 Sec
Values:
0.00, 0.25, 0.50, 0.75, 1.00
Alarm
O/P Alarm OFF High, OFF
POWER ALARM OFF ON, OFF
Sat ALARM OFF ON, OFF
dELAy 20 Sec Range: 0 -3600Sec
COMMS ALARM ON ON, OFF
Meter Pass Code 7452 Range: 0000 to 9999
11. Settings table
*
*
For imperial figures, see the table on the following page
*