7.5.2.1 PULSE
This enables or disable the pulsed output, by selecting yes or no.
7.5.2.2 SORCE
This selects the source data for the pulsed output.
The source data can be either unit mass per pulse (tOtAL) or unit energy per pulse (ENRGy).
7.5.2.3 NUM/PULSE
This allows the total mass, or energy, which is equivalent to one pulse to be configured. Units are
dependent on the UNIt setting. (Metric or Imperial).
7.5.2.4 PULSE WIDTH
This allows the width of the pulse to be set. The width can be set in 0.01 second increments from 0.02 seconds to a
maximum of 0.2 seconds.
7.5.2 Pulse Output

(in kg or Tons, MWh or MBtu)
(Must not exceed 4 pulses/sec)