IM-P402-93 AB Issue 7
21
The controller is supplied with the following default settings:-
Security code 00
Control type Proportional
Pump action In (boiler water level control, for example)
Input level 0 - 6 V
Lvlinput O/rngdet (level input out of range detect) No
Set point 50 %
Control band 50 %
Alarm low 00 %
High alarm 99 %
Alarm delay 00 s
Lockout on alarm No
Valve drive Relay
Water meter No
Steam meter No