EasyManua.ls Logo

Stager YDE12000E - Page 8

Default Icon
29 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lube oil type SAE 15W-30, 15W-40 SAE 15W-30, 15W-40 SAE 15W-30, 15W-40
Fuel type Diesel 0#(summer) -10#(winter) -35# (chilly winter)
Fuel tank capacity 25 L 25 L 25 L
Fuel consumption ≤ 340 g/kW.h ≤ 340 g/kW.h ≤ 340 g/kW.h
Noise level (LwA) 97 dB(A) 93 dB(A) 93 dB(A)
Three-phase generator sets:
Model
Item
YDE12000E3 YDE12000T3 YDE15000T3
Rated frequency 50 Hz 50 Hz 50 Hz
Rated power 12 kVA 12 kVA 13 kVA
Maximum power 13 kVA 13 kVA 14 kVA
Rated voltage (CA) 400/230 V 400/230 V 400/230 V
Rated current (CA) 17.3 A 17.3 A 18.8 A
Rated speed 3000 r/min 3000 r/min 3000 r/min
Phase no. three-phase three-phase three-phase
Power factor (cos Φ) 0.8 (lag) 0.8 (lag) 0.8 (lag)
Excitation mode AVR (self-excited, automatic voltage regulator)
Voltage output (DC) 12V - 36Ah 12V - 36Ah 12V - 36Ah
Structure mode Open frame Silent Ultra silent
Insulation class F F F
Pole no. 2 2 2
Connecting Mode Transmission shaft rigid connection
Weight 185 kg 260 kg 260 kg
Dimensions (Lxlxh) 1000 x 630 x 700 mm 1095 X 650 X 780 mm 1095 X 650 X 780 mm
Engine model YD2V88 YD2V88 YD2V92F
Engine type
Diesel engine, V-twin, 4-stroke, direct injection, air-
cooled
Diesel engine, V-two, vertical,
4-stroke, air-cooled
Engine rated power 13.8 kW / 3000 rpm 13.8 kW / 3000 rpm 14.8 kW / 3000 rpm
Bore x stroke 88 x 75 mm 88 x 75 mm 92x75 mm
Displacement 912 ml 912 ml 997 ml
Compression ratio 20:1 20:1 20:1
Cooling system air-cooled air-cooled air-cooled
Lube oil capacity 2.3 L 2.3 L 2.4 L
Lube oil type SAE 15W-30, 15W-40 SAE 15W-30, 15W-40 SAE 15W-30, 15W-40
Fuel type Diesel 0#(summer) -10#(winter) -35# (chilly winter)
Fuel tank capacity 25 L 25 L 25 L
Fuel consumption ≤ 340 g/kW.h ≤ 340 g/kW.h ≤ 340 g/kW.h
Noise level (LwA) 97 dB(A) 93 dB(A) 93 dB(A)
Note:
*The displayed noise level indicates the noise emission level of the equipment, but it does not represent a safe
working noise level.
Factors affect the practical noise level include: the ambient condition and other noise source, such as the quantity of
working machine or the working hours in noisy condition. Furthermore, the sound exposure level varies among different
countries.
It is mandatory to wear helmets.
* The specification data is subject to change without notice.
Ver. 3/Rev. 2; Data: 8.08.2022 34