Example: electrical connection of a thermostat (ambient air monitoring) of a differential thermostat connected to
the deposit and three-way valve to a relay box.
Figure 51 - Electrical connection of a thermostat (ambient air monitoring) of a differential thermostat connected to the domestic hot water and 2 way motorized valves
Connection to central heating radiators with another boiler support and sanitary water combined with solar panel
Figure 52 - Connection to central heating radiators with another boiler support and sanitary water combined with solar panel
Note:
- The differential thermostat must have a hysterisis of 15 to 25 °C.
- Hydro independent “Off” (water temperature-controlled regulation), put the boiler in “manual” mode and power level to “5”
- Modulating pump “On”
- Water sensing inhibition “On”
- Alternative hydro shutdown “On”
- Pump “On” = 50 °C
- Pump “Off” = same or thermostat temperature 1°C below the temperature differential thermostat.
When using the generator with differential thermostat the machine must be connected in the CONNECTION “Remote”.
Calculation Buffer Tank: For pellet boiler it’s recommended that the buffer tank has 20l/kW.
NOTE: For Tiemme electronics when connecting the stove to the inertia tank it is necessary to change the following parameters:
P77=04
A01=04
(Contact technical support if necessary)
Connecting underfloor heating in conjunction with another boiler support and sanitary water combined with solar