COMMISSIONING
Settings
42 | WPM www.stiebel-eltron.com
Menu item/parameter Options Unit Min. Max. Standard System value
HZG PWM OFF | ON
HZG 0-10 V OFF | ON
HEATING CURVE GAP K 1 15 3
SET BOILER TEMPERATURE °C 35 90
BLOCKING TIME EVU OFF h 1 10
LOWER APP LIMIT HZG OFF °C -19.5 40 -19.5 °C
DUAL MODE TEMP HZG °C -20 40 -20 °C
HZG PWM K min 10 100 3
HZG 0-10 V K min 10 100
ELECTRIC REHEATING
LOWER APP LIMIT HZG OFF °C -20 40 -20 °C
DUAL MODE TEMP HZG °C -20 40 -20 °C
NUMBER OF STAGES 0 3 3
DELAY min 1 60 60 min
DHW
DHW TEMPERATURES
COMFORT TEMPERATURE °C 10 60 50 °C
ECO TEMPERATURE °C 10 60 50 °C
STANDARD SETTING
DHW HYSTERESIS K 1 10 5 K
DHW STAGES 1 6 1
AUTOMATIC DHW CONTROL OFF | ON OFF
OUTSIDE TEMPERATURE °C -5 30
WW LEARNING FUNCTION OFF | ON OFF
COMBI CYLINDER OFF | ON OFF
WW OUTPUT WP
WW OUTPUT SUMMER kW 5 15 10 kW
WW OUTPUT WINTER kW 5 15 10 kW
MAXIMUM FLOW TEMPERATURE °C 20 75 75 °C
PASTEURISATION OFF | ON OFF
SET TEMPERATURE
with 2nd heat generator (2.WE)
°C
°C
60
60
65
75
ELECTRIC REHEATING
DUAL MODE TEMP WW °C -20 40 -20 °C
LOWER APP LIMIT WW OFF °C -20 40 -20 °C
EXTERNAL HEAT SOURCE
OFF
SUPPORTED OFF | ON
ALONE OFF | ON
INDEPENDENT OFF | ON
DUAL MODE TEMP WW °C -20 40 -20 °C
LOWER APP LIMIT WW OFF °C -19.5 40 -19.5 °C
WW PWM % 0 100
WW 0-10 V 0 10
DHW CIRCULATION
DEMAND OFF | ON
PROGRAM OFF | ON
PROGRAM + INPUT OFF | ON
PROGRAM + SENSOR OFF | ON
SET TEMPERATURE °C 35 60
HYSTERESIS K 0.5 5
HYBRID MODULE
2ND HEAT GENERATOR TYPE
GAS CONDENSING OFF | ON ON
GAS NON-CONDENSING OFF | ON OFF
OIL CONDENSING OFF | ON OFF
OIL NON-CONDENSING OFF | ON OFF
2ND HEAT GENERATOR SETTING
SET TEMPERATURE 35 90 70
HYSTERESIS 1 10 5
MIXER DYNAMICS 30 240 200
HEATING CURVE GAP 1 10 5
SOFT START TEMPERATURE 40 60 50