COMMISSIONING
Settings
www.stiebel-eltron.com WPM | 43
Menu item/parameter Options Unit Min. Max. Standard System value
 DELAY Minutes 1 240 60
 IDLE TIME Minutes 1 120 10
 TYPE OF OPTIMISATION
 ECO DRIVE 0 10 0
 ECONOMICAL
 PEAK TARIFF PRICE 1 99 23.1
 OFF-PEAK TARIFF PRICE 1 99 19.1
 GAS PRICE 1 99 5.8
 OIL PRICE 1 99 5.8
 ECOLOGICAL
 ELECTRICITY CO2 EMISSIONS 1 600 530
 GAS CO2 EMISSIONS 1 600 200
 OIL CO2 EMISSIONS 1 600 290
 HEAT PUMP SETTING
 LOWER APP LIMIT OFF 40 -20
 BLOCKING TIME EVU OFF 10 1
COOLING (with FE 7)
 COOLING OFF | ON OFF
 COOLING MODE
 PASSIVE COOLING OFF | ON OFF
 ACTIVE COOLING OFF | ON OFF
 STANDARD SETTING
 COOLING STAGES 1 6 6
 COOLING LIMIT °C 15 40 20 °C
 COOLING CAPACITY kW 3 10 8 kW
 ACTIVE COOLING OFF | ON
 AREA COOLING OFF | ON OFF
 SET FLOW TEMPERATURE °C 7 25 15 °C
 FLOW TEMP HYSTERESIS K 1 5 5 K
 SET ROOM TEMPERATURE °C 20 30 25 °C
 DYNAMICS ACTIVE 1 10 10
 DYNAMICS PASSIVE 0 10
 FAN COOLING OFF | ON OFF
 SET FLOW TEMPERATURE °C 7 25 15 °C
 FLOW TEMP HYSTERESIS K 1 5 5 K
 SET ROOM TEMPERATURE °C 20 30 25 °C
 DYNAMICS ACTIVE 1 10 10
 DYNAMICS PASSIVE 0 10
 PASSIVE COOLING OFF | ON
 AREA COOLING OFF | ON OFF
 SET FLOW TEMPERATURE °C 7 25 15 °C
 FLOW TEMP HYSTERESIS K 3 10 5 K
 SET ROOM TEMPERATURE °C 20 30 25 °C
 DYNAMICS PASSIVE 1 10
 FAN COOLING OFF | ON OFF
 SET FLOW TEMPERATURE °C 7 25 15 °C
 FLOW TEMP HYSTERESIS K 3 10 5 K
 SET ROOM TEMPERATURE °C 20 30 25 °C
 DYNAMICS PASSIVE 1 10
COOLING (with FET)
 COOLING OFF | ON
 COOLING MODE
 PASSIVE COOLING OFF | ON
 ACTIVE COOLING OFF | ON
 STANDARD SETTING
 COOLING STAGES 1 6
 COOLING LIMIT °C 15 40
 COOLING CAPACITY kW 3 10
 FLOW TEMP HYSTERESIS K 3 10
 DYNAMICS ACTIVE 1 10
 DYNAMICS PASSIVE 0 10
 COOLING CIRCUIT 1 OFF | ON