COMMISSIONING
Settings
www.stiebel-eltron.com WPM | 43
Menu item/parameter Options Unit Min. Max. Standard System value
DELAY Minutes 1 240 60
IDLE TIME Minutes 1 120 10
TYPE OF OPTIMISATION
ECO DRIVE 0 10 0
ECONOMICAL
PEAK TARIFF PRICE 1 99 23.1
OFF-PEAK TARIFF PRICE 1 99 19.1
GAS PRICE 1 99 5.8
OIL PRICE 1 99 5.8
ECOLOGICAL
ELECTRICITY CO2 EMISSIONS 1 600 530
GAS CO2 EMISSIONS 1 600 200
OIL CO2 EMISSIONS 1 600 290
HEAT PUMP SETTING
LOWER APP LIMIT OFF 40 -20
BLOCKING TIME EVU OFF 10 1
COOLING (with FE 7)
COOLING OFF | ON OFF
COOLING MODE
PASSIVE COOLING OFF | ON OFF
ACTIVE COOLING OFF | ON OFF
STANDARD SETTING
COOLING STAGES 1 6 6
COOLING LIMIT °C 15 40 20 °C
COOLING CAPACITY kW 3 10 8 kW
ACTIVE COOLING OFF | ON
AREA COOLING OFF | ON OFF
SET FLOW TEMPERATURE °C 7 25 15 °C
FLOW TEMP HYSTERESIS K 1 5 5 K
SET ROOM TEMPERATURE °C 20 30 25 °C
DYNAMICS ACTIVE 1 10 10
DYNAMICS PASSIVE 0 10
FAN COOLING OFF | ON OFF
SET FLOW TEMPERATURE °C 7 25 15 °C
FLOW TEMP HYSTERESIS K 1 5 5 K
SET ROOM TEMPERATURE °C 20 30 25 °C
DYNAMICS ACTIVE 1 10 10
DYNAMICS PASSIVE 0 10
PASSIVE COOLING OFF | ON
AREA COOLING OFF | ON OFF
SET FLOW TEMPERATURE °C 7 25 15 °C
FLOW TEMP HYSTERESIS K 3 10 5 K
SET ROOM TEMPERATURE °C 20 30 25 °C
DYNAMICS PASSIVE 1 10
FAN COOLING OFF | ON OFF
SET FLOW TEMPERATURE °C 7 25 15 °C
FLOW TEMP HYSTERESIS K 3 10 5 K
SET ROOM TEMPERATURE °C 20 30 25 °C
DYNAMICS PASSIVE 1 10
COOLING (with FET)
COOLING OFF | ON
COOLING MODE
PASSIVE COOLING OFF | ON
ACTIVE COOLING OFF | ON
STANDARD SETTING
COOLING STAGES 1 6
COOLING LIMIT °C 15 40
COOLING CAPACITY kW 3 10
FLOW TEMP HYSTERESIS K 3 10
DYNAMICS ACTIVE 1 10
DYNAMICS PASSIVE 0 10
COOLING CIRCUIT 1 OFF | ON