EasyManua.ls Logo

Structural Concepts Oasis MI44RF - CAREL CONTROLLER: Summary Table of Operating Parameters

Structural Concepts Oasis MI44RF
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26 26
Summary Table of Operating Parameters
CAREL PROGRAMMABLE CONTROLLER, CONTD
Integrated Electronic
Microprocessor Controller
CODE PARAMETER UOM* TYPE MINIMUM MAXIMUM DEFAULT
/5
Select Celsius (°C) or Fahrenheit (°F)
flag C 0 1
/c1 Calibration of probe 1 °C/°F C -20 20
/c2 Calibration of probe 2 °C/°F C -20 20
St Temperature set point °C/°F F r2 r1
rd Control delta °C/°F F 20 0.1
dl Interval between defrosts hours F 0 250
d4
Defrost activated when instrument is
switched on**
- - 0 1
dt1 End defrost temperature, evaporator °C/°F F -50 200
dP1 Maximum defrost duration, evaporator min F 1 250
d6 Display on hold during defrost - C 0 2
dd Dripping time after defrost min F 0 15
d/1 Display of defrost probe 1 °C/°F F - -
For Case
Specific
Defaults
See Serial
Label
Located
Near
Electrical
Access
On Your
Case.
For
Additional
Technical
Information
Call
Structural
Concepts
Technical
Service
Dept. at
1(800)
433.9490
Ext. 1
* Unit Of Measure
This data derived from Carel® Controller Material:
ir33 +030220441 - rel. 2.0 - 01.05.2006.
Structural Concepts Document - Revision C Date: 1.4.2022
** Case will go into defrost ONLY when case is turned off and then
back on when probe is reading below 45 °F.

Related product manuals