EasyManua.ls Logo

Studer RCC-03 - Page 93

Studer RCC-03
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Studer Innotec SA
RCC-02/-03
User manual V4.4.0 89
Level
User
ref.
Parameter
Unit
12
24
48
Mod.
value
Factory
Min
Max
Factory
Min
Max
Factory
Min
Max
Expert
1262
Power level 2 (AUX 1)
% Pnom
80
20
120
80
20
120
80
20
120
Expert
1263
Time delay 2 (AUX 1)
min
5
0
60
5
0
60
5
0
60
Expert
1264
Inverter power level 3 activate (AUX 1)
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1265
Power level 3 (AUX 1)
% Pnom
50
20
120
50
20
120
50
20
120
Expert
1266
Time delay 3 (AUX 1)
min
30
0
60
30
0
60
30
0
60
Expert
1267
Inverter power level to deactivate (AUX 1)
% Pnom
40
20
120
40
20
120
40
20
120
Expert
1268
Time delay to deactivate (AUX 1)
min
5
0
60
5
0
60
5
0
60
Inst.
1503
Contact active according to battery temperature
(AUX 1) With BSP or BTS
Inst.
1446
Contact activated with the temperature of
battery (AUX 1)
No/Yes
No
-
-
No
-
-
No
-
-
Inst.
1447
Contact activated over (AUX 1)
°C
3
-10
50
3
-10
50
3
-10
50
Inst.
1448
Contact deactivated below (AUX 1)
°C
5
-10
50
5
-10
50
5
-10
50
Expert
1501
Contact active according to SOC (AUX 1) Only
with BSP
Expert
1439
Contact activated with the SOC 1 of battery
(AUX 1)
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1440
Contact activated below SOC 1 (AUX 1)
% SOC
50
0
100
50
0
100
50
0
100
Expert
1581
Delay 1 (AUX 1)
h
12
0
99
12
0
99
12
0
99
Expert
1582
Contact activated with the SOC 2 of battery
(AUX 1)
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1583
Contact activated below SOC 2 (AUX 1)
%
30
0
100
30
0
100
30
0
100
Expert
1584
Delay 2 (AUX 1)
h
0.2
0
99
0.2
0
99
0.2
0
99
Expert
1585
Contact activated with the SOC 3 of battery
(AUX 1)
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1586
Contact activated below SOC 3 (AUX 1)
%
20
0
100
20
0
100
20
0
100
Expert
1587
Delay 3 (AUX 1)
h
0
0
99
0
0
99
0
0
99
Expert
1441
Contact deactivated over SOC (AUX 1)
% SOC
90
0
100
90
0
100
90
0
100
Expert
1588
Delay to deactivate (AUX 1)
h
0.2
0
10
0.2
0
10
0.2
0
10
Expert
1589
Deactivate if battery in floating phase (AUX
1)
No/Yes
Yes
-
-
Yes
-
-
Yes
-
-
Expert
1512
Security, maximum time of contact (AUX 1)
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1514
Maximum time of operation of contact (AUX 1)
min
600
10
1200
600
10
1200
600
10
1200
Expert
1569
Reset all settings (AUX 1)
-
-
-
-
-
-
-
-
-
Expert
1310
AUXILIARY CONTACT 2
Expert
1311
Operating mode (AUX 2)
Text
Reversed
automatic
-
-
Reversed
automatic
-
-
Reversed
automatic
-
-
Expert
1498
Combination of the events for the auxiliary
contact (AUX 2)
Text
Any (Function
OR)
-
-
Any
(Function
OR)
-
-
Any
(Function
OR)
-
-
Expert
1312
Temporal restrictions (AUX 2)
Expert
1313
Program 1 (AUX 2)

Table of Contents

Other manuals for Studer RCC-03