Studer Innotec SA
RCC-02/-03
User manual V4.4.0 93
Level
User
ref.
Parameter
Unit
12
24
48
Mod.
value
Factory
Min
Max
Factory
Min
Max
Factory
Min
Max
Expert
1493
Number of starting attempts
5
0
20
5
0
20
5
0
20
Expert
1492
Starter pulse duration (with AUX2)
sec
3
1
20
3
1
20
3
1
20
Expert
1494
Time before a starter pulse
sec
3
1
20
3
1
20
3
1
20
Expert
1574
Main contact hold/interrupt time
sec
0
0
30
0
0
30
0
0
30
Expert
1101
SYSTEM
Expert
1537
Remote entry (Remote ON/OFF)
Expert
1545
Remote entry active
Closed/Open
Open
-
-
Open
-
-
Open
-
-
Expert
1538
Prohibits transfert relay
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1539
Prohibits inverter
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1540
Prohibits charger
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1541
Prohibits Smart-Boost
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1542
Prohibits grid feeding
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1566
Using a secondary value for the maximum
current of the AC source
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1567
Second maximum current of the AC source
(Input limit)
Aac
16
2
50
16
2
50
16
2
50
Expert
1554
Decrease of the max. current of the source
with input voltage activated by command
entry
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1576
ON/OFF command
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1578
Activated by AUX1 state
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1579
Prohibits battery priority
No/Yes
No
-
-
No
-
-
No
-
-
Inst.
1600
Disable minigrid mode
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1296
Batteries priority as energy source
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1297
Battery priority voltage
Vdc
12.9
9.5
18
25.8
19
36
51.6
37.9
72
Expert
1565
Buzzer alarm duration
min
0
0
60
0
0
60
0
0
60
Expert
1129
Auto restarts
Expert
1130
After battery undervoltage
No/Yes
Yes
-
-
Yes
-
-
Yes
-
-
Expert
1304
Number of batteries undervoltage allowed
before definitive stop
3
1
20
3
1
20
3
1
20
Expert
1404
Time period for batteries undervoltages
counting
sec
0
0
3000
0
0
3000
0
0
3000
Expert
1305
Number of batteries critical undervoltage
allowed before definitive stop
10
1
20
10
1
20
10
1
20
Expert
1405
Time period for critical batteries
undervoltages counting
sec
10
0
3000
10
0
3000
10
0
3000
Expert
1131
After battery overvoltage
No/Yes
Yes
-
-
Yes
-
-
Yes
-
-
Expert
1132
After inverter or Smart-Boost overload
No/Yes
Yes
-
-
Yes
-
-
Yes
-
-
Expert
1533
Delay to restart after an overload
sec
5
2
120
5
2
120
5
2
120
Expert
1134
After overtemperature
No/Yes
Yes
-
-
Yes
-
-
Yes
-
-
Expert
1111
Autostart to the battery connection
No/Yes
No
-
-
No
-
-
No
-
-

Table of Contents