EasyManua.ls Logo

Stulz C2020 - Page 36

Stulz C2020
109 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN/07.2013/58/36
I141. Polarity digit out R10
Select the polarity of digital output R10:
0 = normally opened 1 = normally closed
0/1 -
I142. Polarity digit out R11
Select the polarity of digital output R11:
0 = normally opened 1 = normally closed
0/1 -
I143. Polarity digit out R12
Select the polarity of digital output R12:
0 = normally opened 1 = normally closed
0/1 -
I144. Polarity digit out R13
Select the polarity of digital output R13:
0 = normally opened 1 = normally closed
0/1 -
I145.
Filter coefficient Analog
ch. IC1
Value of the filter coefficient for the analogic channel IC1. This
coefficient is used to calculate the average of measurement of
this channel.
0/200 -
I146.
Filter coefficient Analog
ch. IC2
Value of the filter coefficient for the analogic channel IC2. This
coefficient is used to calculate the average of measurement of
this channel.
0/200 -
I147.
Filter coefficient Analog
ch. IC3
Value of the filter coefficient for the analogic channel IC3. This
coefficient is used to calculate the average of measurement of
this channel.
0/200 -
I148.
Filter coefficient Analog
ch. T1
Value of the filter coefficient for the analogic channel T1. This
coefficient is used to calculate the average of measurement of
this channel.
0/200 -
I149.
Filter coefficient Analog
ch. T2
Value of the filter coefficient for the analogic channel T2. This
coefficient is used to calculate the average of measurement of
this channel.
0/200 -
I150.
Filter coefficient Analog
ch. T3
Value of the filter coefficient for the analogic channel T3. This
coefficient is used to calculate the average of measurement of
this channel.
0/200 -
I151.
Filter coefficient Analog
ch. T4
Value of the filter coefficient for the analogic channel T4. This
coefficient is used to calculate the average of measurement of
this channel.
0/200 -
I152. PASSWORD -
In the next table there are the analog channels which can be connected.
IRH Internal relative humidity
PC Condenser pressure
ERH External relative humidity
TE Evaporator temperature
TC Condenser temperature
TI Internal temperature
TAE External air temperature
TM Delivery air Temperature
TM1 Delivery air Temperature for Comfort 1 in Custom 13
TM2 Delivery air Temperature for Comfort 2 in Custom 13
TI1 Internal temperature 1 in Custom 9
TI2 Internal temperature 2 in Custom 9
NO Conn. No connection

Table of Contents

Related product manuals